516 

 

UOSA utilized an energy performance contract to identify, evaluate and install various energy 
conservation measures throughout the site that included: combined heat & power electrical generation 
using biogas; aeration basin high efficiency turbo blowers; and site wide lighting improvements. 

UOSA actively participates in numerous WERF, WRRF, WRF and other research activities and projects; 
Active/Open (9); Pending Award (6); Closed (2); and Not Awarded (5). 

Power and fuel sub-metering is installed and monitored for critical process units at the building, sub-
building and specific equipment level (Ex. aeration blowers, pumps. biosolids pelletizers; scrubbers, 
CH&P unit, boilers, etc.) 

Utilization of energy conserving equipment wherever possible (e.g., utilization of peak shaving 
equipment to reduce usage). UOSA operates three emergency generators for emergency power back-up 
and for peak shaving purposes. 

Installation of ultra-high efficiency turbo blowers for aeration. 

Retrofit of site lighting with high efficiency lamps, ballasts and occupancy sensors. 

Use of flow equalization to spread/distribute peak flows, conserve energy and to reduce power costs. 

Performance Measures & Results 

Your Performance Measure(s) 

Your Results (quantitative or qualitative) 

KWh reductions in site energy use/intensity – to date or 
anticipated in the future (e.g., change in energy required per 
million gallons treated, or change in energy required per hour of 
pump operation)  

38% reduction kWh/MG since 2005. 
27% reduction kWh/MG since 2010. 
FY-11 3409 kWh/MG 
FY-12 3363 kWh/MG 
FY-13 3247 kWh/MG 
FY-14 2623 kWh/MG 
FY-15 2652 kWh/MG 
FY-16 2472 kWh/MG 

Translation of energy use/intensity reductions to greenhouse gas 
emission reductions – to date and anticipated in the future 

To Date: 55,785 tons since 2005. 
Ongoing: 12,000 tons per year. 

Current and anticipated investment (in USD) in energy efficiency 
projects or activities, and anticipated savings (in USD) 

Current Investment: $6,900,000 
Savings Since 2005: $4,956,547 

Electrical and natural gas sub-metering is conducted for critical 
process units
 

Sub-metering is provided in all buildings and 
in critical process units such as CHPCU, 
turbo blowers used for aeration, rotary 
pelletizers, pumps, lighting, and HVAC. 

Utilization of peak shaving equipment to reduce usage and costs 
(Hrs/Yr; $/Yr) 

Typical Utilization: 200-400 gen-hrs per year 
Typical Savings: $90-$130K per year  
FY-16 Savings: $92K 

Reduce Chemical Sludge to Landfill (Yds/MG) 

FY-11 669 Cubic Yards/MG 
FY-12 496 Cubic Yards/MG 
FY-13 605 Cubic Yards/MG 
FY-14 292 Cubic Yards/MG 
FY-15 511 Cubic Yards/MG 

Reduce Amount of Land Applied Class B Biosolids 

Reduced 95% since 2005 

Increase Amount of Land Applied Class A EQ Biosolids 

Increased  531% since 2005 

Decrease Chemical Use and Chemical Cost ($/MG) 

Reduced $59.42/MG since 2006; Represents 
a 31% reduction in chemical costs ($/MG).